ADTRAN 3192 User Manual

Size:
278.9 Kb
Download

3192

4-PairLPU

P/N: 1181501L2

CLEI: SIPQ0CVF_ _

LPU

1181501L2

POWER

UNDER VOLTAGE

GROUND FAULT

OVERLOAD

UNDER CURRENT

*61181501L2-22C*

C A U T I O N !

SUBJECT TO ELECTROSTATIC DAMAGE OR DECREASE IN RELIABILITY.

HANDLING PRECAUTIONS REQUIRED.

3192 4-PairLine Power Unit

61181501L2-22C

0510

GENERAL

This job aid provides information for the installation, function, and operational use of the ADTRAN® 3192 Line Power Unit (LPU). The LPU (P/N 1181501L2) is designed to provide power for the Total Access® 1124/1148 Line Powered Digital Subscriber Line Access Multiplexer (DSLAM).

DESCRIPTION

Each ADTRAN LPU provides up to 100 watts of power to an associated DSLAM on a one-to-onebasis. The LPU can reside either in a Central Office (CO) or be installed in a remote facility in close proximity to the associated DSLAM. The LPU provides ±145 VDC power and can span distances up to 60 kft (approximately 11 miles).

Each LPU occupies any two adjacent slots in a 3192 shelf. Slots not occupied by an LPU can house standard channel cards. Total slot population is limited by the maximum input current of the 3192 shelf.

The LPU receives –48VDC at a maximum of 2.6 amps from the chassis backplane and outputs to four Tip and Ring power pairs. Voltage potential per pair is Tip +145 VDC and Ring–145VDC (290 VDC combined).

The total power wiring pair requirement is based on transmission distance to the remote location.

FUSES

Power input to the LPU is fused at 4.0 amps; Tip and Ring power output is fused at 1.5 amps each. Fuses are not replaceable.

INSTALLATION

After unpacking the unit, inspect it for damage. If damage is noted, file a claim with the carrier, and then contact ADTRAN. For more information, refer to the warranty.

The LPU installs in any two adjacent slots in a 3192 shelf.

WARNING: Adhere to static discharge precautions when handling circuit cards.

To insert the LPU, perform the following steps:

1.If present, remove the blank panel from the appropriate module slot of the chassis.

2.Pull the ejector latch, located on the lower right-handside of the LPU front panel, from its closed position.

3.Hold the LPU by the front panel while supporting the bottom edge of the module with the ejector latch opened to engage the chassis edge.

4.Align the LPU card edges to fit in the lower and upper guide grooves for the access module slot.

5.Slide the LPU into the module slot. Simultaneous thumb pressure at the top (above the POWER LED) and at the bottom (below the electrostatic caution symbol) of the front panel ensures that the LPU is firmly positioned against the backplane of the chassis.

6.Secure the LPU in place by pushing in on the ejector latch.

Upon installation, the LPU initiates a self-test.Once the power upself-testis completed, the front panel LEDs reflect the true state of the hardware.

LED INDICATION

Five front panel LEDs provide status for the LPU. The POWER LED is green; its normal condition is on. All other LEDs are red; their normal condition is off. LEDs are as follows:

LED

Status

Description

POWER

On

LPU receiving –48VDC

 

Off

LPU not receiving power or supply fuse failed

UNDER VOLTAGE

On

< 115 VDC per T or R (< 230 VDC per T/R pair)

 

Off

Voltage normal: ±145 V per T/R (± 5%)

GROUND FAULT

On

Ground fault detected

 

Off

No ground fault

OVERLOAD

On

> 0.4 amps at 290 VDC

 

Off

No overload

UNDER CURRENT

On

< 0.04 amps

 

Off

Current normal

3192 4-PairLine Power Unit

PRICING AND AVAILABILITY 800.827.0807 TECH SUPPORT 800.726.8663

RETURN FOR REPAIR 256.963.8722 www.adtran.com

61181501L2-22C

3192 LPU EDGE CONNECTOR WIRING

Left Slot

1

2

3

4

5

6

7

8

9

10 ABCDEFHJKL

-48VReturn

Pair 1 Ring

-48V

Pair 2 Ring

Fuse Alarm (to Alarm Module)

Pair 1 Tip

Frame Ground

Pair 2 Tip

Right Slot

1

2

3

4

5

6

7

8

9

10 ABCDEFHJKL

-48VReturn

Pair 5 Ring

-48V

Pair 6 Ring

Pair 5 Tip

Frame Ground

Pair 6 Tip

NOTE: Connect only those output pairs required to meet power requirements of the Total Access 1124 DSLAM based on the transmission distance.

COMPLIANCE

WARNING: Risk of electric shock. Max voltages of ±145 VDC with respect to ground, and 290 VDC across the loops may be present on telecommunications wiring. Ensure chassis ground is properly connected.

This product is intended for installation in restricted access locations only and in equipment with a type “B” or “E” enclosure.

Code

Input

Output

Power Code

F

C

Telecommunication Code (TC)

X

Installation Code (IC)

A

 

 

 

This product provides span powering voltage (±145 VDC nominal, GFI protection < 0.005 amps). This product is NRTL Listed to the applicable UL standards.

MAINTENANCE

The LPU does not require maintenance for normal operation. ADTRAN does not recommend that repairs be attempted in the field. Repair services are obtained by returning the defective unit to ADTRAN. Refer to Warranty section for further information.

SPECIFICATIONS

The following table lists the LPU specifications:

Specification

Description

Physical

Dimensions:

Height: 4.75 inches

 

Width: 1.375 inches

 

Depth: 10.0 inches

Weight:

11 ounces

Environmental

Max operating temperature:

–40°Cto +70°C

Max storage temperature:

–40°Cto +85°C

Relative humidity:

95% non condensing

Electrical

Input power:

100 watts max

Operating voltage:

–42to–56VDC

Output voltage:

±145 VDC per T/R pair (290 VDC total)

Maximum output current:

Rated: 0.345 amps

 

Maximum: 0.4 amps (total across all output pairs)

 

 

Warranty: ADTRAN will replace or repair this product within the warranty period if it does not meet its published specifications or fails while in service. Warranty information can be found online atwww.adtran.com/warranty.